Název: Mould Risk on Wall Surface in Partly Underground Technical Room
Autoři: Nováková, Iva ; Šikula, Ondřej
Typ dokumentu: Příspěvky z konference
Jazyk: eng
Nakladatel: Vysoké učení technické v Brně,Fakulta stavební
Abstrakt: This conference article aims at the indoor climate in the technical room of an underground water reservoir. This indoor climate is specific by high relative humidity (average 75.2% r.h.) and low air temperature (average 13.6 °C). Therefore, this research study focuses on surface condensation and mould risk on the partly underground wall in the technical room. The experimental research combines long-term monitoring (22 months). Long-term of indoor climate and thermal numerical simulation. The experimental measurement shows condensation risk on the indoor wall surface, and the unsteady 2D numerical simulation in software Calculation Area 4.0e shows temperature fluctuation on indoor wall surfaces. Finally, the empirical VVT model predicts mould risk on the indoor wall surface for the over-terrain part in autumn and summer for the under-terrain part. 
Klíčová slova: experimental measurement; high relative humidity; mould risk ; numerical simulation; Water reservoir
Zdrojový dokument: Juniorstav 2024: Proceedings 26th International Scientific Conference Of Civil Engineering, ISBN 978-80-86433-83-7

Instituce: Vysoké učení technické v Brně (web)
Informace o dostupnosti dokumentu: Plný text je dostupný v Digitální knihovně VUT.
Původní záznam: https://hdl.handle.net/11012/245453

Trvalý odkaz NUŠL: http://www.nusl.cz/ntk/nusl-614417

 Záznam vytvořen dne 2024-05-12, naposledy upraven 2024-05-12.


Není přiložen dokument