Název: Comparison Of Arc Erosion Coefficients
Autoři: Piska, Jakub
Typ dokumentu: Příspěvky z konference
Jazyk: eng
Nakladatel: Vysoké učení technické v Brně, Fakulta elektrotechniky a komunikačních technologií
Abstrakt: The problem of nonunified approaches to giving arc erosion ratios is addressed for the application of molded case circuit breakers (MCCBs) in the range 6.5-10 kA. Charge, Joule’s integral and arc energy are compared as possible quantities to use for ratios of mass loss. The linearity of the relationship of mass loss to those quantities was used as the main metric. By this metric the ratio to charge was chosen as the most reliable one. But this relation was constant only for fixed contacts with arcrunners. For the moving contact, the mass loss ratio was a linear function of the effective value of the passing current.
Klíčová slova: arc erosion; erosion ratios; mass loss; MCCB
Zdrojový dokument: Proceedings II of the 26st Conference STUDENT EEICT 2020: Selected papers, ISBN 978-80-214-5868-0

Instituce: Vysoké učení technické v Brně (web)
Informace o dostupnosti dokumentu: Plný text je dostupný v Digitální knihovně VUT.
Původní záznam: http://hdl.handle.net/11012/200629

Trvalý odkaz NUŠL: http://www.nusl.cz/ntk/nusl-447681


Záznam je zařazen do těchto sbírek:
Školství > Veřejné vysoké školy > Vysoké učení technické v Brně
Konferenční materiály > Příspěvky z konference
 Záznam vytvořen dne 2021-07-25, naposledy upraven 2021-08-22.


Není přiložen dokument
  • Exportovat ve formátu DC, NUŠL, RIS
  • Sdílet